Permit: T06CM02254

Parcel: 108251990

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T06CM02254

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
03/14/2007 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
03/08/2007 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GROUND RODS TO BE 6' APART MINIMUM -- NEC 250.56
NEC 250.53 B

WILL NEED TO PAY REINSPECTION FEE
03/06/2007 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*
WORK NOT READY -- WILL NEED TO PAY REINSPECTION FEE