Permit: T06CM02254

Parcel: 108251990

Inspection Status: Approved

Inspection History: ROOF NAILING

Permit Number - T06CM02254

Inspection Description - ROOF NAILING

Inspection Status - Approved

Date Description Inspector Results Comments
12/04/2006 ROOF NAILING Approved IVRS - Inspection :*
10/16/2006 ROOF NAILING Not ready for Inspection IVRS - Inspection :*
STRONGBACK REQUIRED ON DRAG TRUSS
09/12/2006 ROOF NAILING Partial Approval OK TO DRY IN -- INCOMPLETE STRUCTURAL INSPECTION NOTES BELOW MAY BE EXPANDED UPON WHEN COMPLETE INSPECTION DONE.

1. PROVIDE RFI FROM ENGINEER ALLOWING "FRAMING" NAILS (.131 DIAMETER) TYPICAL OF KEYNOTE 8 DETAIL 204/S4.1
2. YOU NEED TO GET YOUR TRUSS DRAWINGS APPROVED & STAMPED.
3. RFI TO DELETE INTERMEDIATE SUPPORT AT SHEAR PANEL DETAIL 18/S1.1
4. THIS BUILDING ONLY GET RFI TO ALLOW DOUBLE LAYER OF SHEATHING.
5. DRAG TRUSS CONNECTION REQUIRES DETAIL
(I CAN'T FIND IT)
6. OK TO DRY IN