Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/21/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/14/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* NO NEED TO CALL FOR FINAL BEFORE EMERGENCY AND POLE LIGHTING CORRECTIONS ARE COMPLETE |
|
| 03/13/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. EMERGENCY LIGHTING WORK IN PROGRESS 2. POLE LIGHTING CORRECTIONS IN PROGRESS |
|
| 03/12/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* INSPECTION FOR SERVICE DRIVE UP BAY 1. EMERGENCY LIGHTING NOT WORKING 2. PROVIDE DISCONNECTING MEANS FOR HEATERS NEC 422.31B 3. CONDUCTORS IN POLE BASES TO BE TERMINATED PER DEVICES LISTING OK TO OCCUPY |
|
| 03/09/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION FOR SHOP AREA 1. IN PARTS ROOM, LOW VOLTAGE FOR NR GUTTER AND RACEWAYS NOT ALLOWED WITH POWER CONDUCTORS EXCEPT AS PERMITTED - NEC 800.52 2. INSURE ELECTRICAL CONTINUITY OF RACEWAYS - NEC 250.97 3. MOTOR/CONTROLLERS TO HAVE PROPER OVER CURRENT PROTECTION - (CHECK NEC 430) PARTIAL INSPECTION ONLY WILL CONTINUE IN SHOP AREA/ELECTRIC ROOMS NEXT INSPECTION |
|
| 03/08/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* PARTIAL INSPECTION ONLY INSPECTION FOR SALES AREA ONLY - NO SHOP/PBX ROOM/ELEC ROOM 1. CHECK TLF TRANSFORMER - NOISY ALL ELSE OK IN SALES AREA. |
|
| 03/07/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR EMERGENCY LIGHTING 1. HAVE 2 HEADS NOT WORKING -- SHOP/SALES 2. HAVE 4 FIXTURES NOT WORKING - DATA ROOM, SHOP HALL & BATHROOMS - ALL OTHER EMERGENCY LIGHTING OK 3. BOND RACEWAYS ON ROOF - NEC 250.97 4. RACEWAYS TO ROOFTOP UNITS FOR FEEDER AND SERVICE RECEPTACLE TO BE COMPLETE TO JUNCTION BOXES - NEC 300.10 |
|
| 03/05/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 03/01/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 314.20 2. WHERE IS POWER FOR DISPOSAL UNDER SINK - PENDING 3. SUPPORT FLEX IN KIOSKS 4. FINISH EXIT LIGHTING OK SALES CUBICLES AND COUNTERS OK SALES OFFICES AND PLAY AREA EXCEPT AS NOTED (FRONT AREA) NO SERVICE LOOKED AT |