Permit: T06CM02252

Parcel: 10408005F


Addresses:

4755 N ORACLE RD 01

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/21/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
03/14/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
NO NEED TO CALL FOR FINAL BEFORE EMERGENCY AND POLE LIGHTING CORRECTIONS ARE COMPLETE
03/13/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. EMERGENCY LIGHTING WORK IN PROGRESS
2. POLE LIGHTING CORRECTIONS IN PROGRESS
03/12/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
INSPECTION FOR SERVICE DRIVE UP BAY
1. EMERGENCY LIGHTING NOT WORKING
2. PROVIDE DISCONNECTING MEANS FOR HEATERS
NEC 422.31B
3. CONDUCTORS IN POLE BASES TO BE TERMINATED PER DEVICES LISTING

OK TO OCCUPY
03/09/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION FOR SHOP AREA
1. IN PARTS ROOM, LOW VOLTAGE FOR NR GUTTER AND RACEWAYS NOT ALLOWED WITH POWER CONDUCTORS EXCEPT AS PERMITTED - NEC 800.52
2. INSURE ELECTRICAL CONTINUITY OF RACEWAYS -
NEC 250.97
3. MOTOR/CONTROLLERS TO HAVE PROPER OVER CURRENT PROTECTION - (CHECK NEC 430)

PARTIAL INSPECTION ONLY

WILL CONTINUE IN SHOP AREA/ELECTRIC ROOMS NEXT INSPECTION
03/08/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
PARTIAL INSPECTION ONLY
INSPECTION FOR SALES AREA ONLY - NO SHOP/PBX ROOM/ELEC ROOM
1. CHECK TLF TRANSFORMER - NOISY ALL ELSE OK IN SALES AREA.
03/07/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
INSPECTION FOR EMERGENCY LIGHTING
1. HAVE 2 HEADS NOT WORKING -- SHOP/SALES
2. HAVE 4 FIXTURES NOT WORKING - DATA ROOM, SHOP
HALL & BATHROOMS - ALL OTHER EMERGENCY LIGHTING OK
3. BOND RACEWAYS ON ROOF - NEC 250.97
4. RACEWAYS TO ROOFTOP UNITS FOR FEEDER AND SERVICE RECEPTACLE TO BE COMPLETE TO JUNCTION BOXES -
NEC 300.10
03/05/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
03/01/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING 314.20
2. WHERE IS POWER FOR DISPOSAL UNDER SINK - PENDING
3. SUPPORT FLEX IN KIOSKS
4. FINISH EXIT LIGHTING

OK SALES CUBICLES AND COUNTERS
OK SALES OFFICES AND PLAY AREA EXCEPT
AS NOTED (FRONT AREA)

NO SERVICE LOOKED AT