Permit: T06CM02252

Parcel: 10408005F


Addresses:

4755 N ORACLE RD 01

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
03/14/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
02/05/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
01/31/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
01/26/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
INSPECTION FOR SERVICE - LETTER OF TORQUE AND PERFORMANCE TEST - RECEIVED TODAY.
DO NOT ENERGIZE ANY LOAD SIDE EQUIPMENT BEFORE APPROVAL FROM ELECTRICAL INSPECTOR.
SAFE OFF/LOCK OUT EQUIPMENT & WIRING AS NEEDED TO INSURE SAFETY.
OK TEP - TEC

INSPECTION FOR CEILING: PARTIAL INSPECTION ONLY
1. GROUND ALL METAL ENCLOSURES - NEC 250.148A
2. HAVE OVERFILLED BOXES - NEC 314.16
3. PROPERLY SUPPORT/SECURE EMT - 358.30
REMOVE CEILING TILES ABOUT ALL ELECTRICAL EQUIPMENT FOR INSPECTION.