Permit: T06CM02191

Parcel: 12101103E

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM02191

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/20/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/19/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
WATER HEATER:
1. TIGHTEN LOOSE FITTINGS
2. SUPPORT CONDUIT
3. MAINTAIN WORKING CLEARANCES 110.26
4. DOOR TO OPEN 90 DEGREES
HALL:
1. WHERE IS EXIT SIGN. SIGN TO BE AS PER 700.12
AS PER PLANS.