Permit: T06CM02179

Parcel: 13615378B

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
05/07/2008 PLUMBING - FINAL Approved IVRS - Inspection :*
04/29/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. PROVIDE CORRECT VENTING OF WATER HEATERS IN LAVATORY WITH INSTALLATION INSTRUCTIONS
2. COMPLETE DRYER INSTALLS

1. PROVIDE A CLEAN BACTERIA REPORT FOR BLD. POTABLE WATER SYSTEM
2. PROVIDE ROOFTOP ACCESS TO UNITS
3. PROVIDE GRAVITY DRAIN FROM SHAMPOO BOWLS TO HAIR TRAPS
4. PROVIDE 8' IN AND 8' OUT INSULATION FOR WATER HEATER IN HAIR SALON
5. SEAL ALL PIPE PENETRATIONS IN & OUT OF BLD.
6. PAINT VENT THRU ROOF
04/03/2008 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
COMPLETE WATER HEATER PIPING IN LAUNDRY, PROVIDE A MEANS TO SUPPLY HOT WATER TO PUBLIC USE LAVS NOT TO EXCEED 110 DEG. COMPLETE EXTERIOR CLEANOUTS TERMINATION CORRECTLY. LIST NOT COMPLETE.

CLOSET FLANGES OK