Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/09/2008 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 04/10/2008 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* 1) NEED REVISION FOR CHANGE TO SERVICE-HAVE AT FINAL 2) REPLACE 225 AMP BREAKER PNL D |
|
| 04/09/2008 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BOND SERVICE GUTTERS 4/0 2. INSTALL MAIN BONDING JUMPERS IN SERVICE DISCONNECTS 3. MARK "SERVICE DISCONNECTS" 4. INSTALL FUSES 5. CABLES IN TERMINATION CAN 6. BOND GAS & WATER 3/0 7. NEED REVISION FOR SERVICE 8. MAIN BREAKER NOT SIZED PROPERLY |