Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T06CM02134
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/13/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
01/19/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CLOSET FLANGES OK EJECTOR PIPING CORRECTED 1. SHALL VERIFY DUPLEX (2) PUMPS IN EJECTOR PER 12/18/06 INSPECTION. |
|
01/17/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* GATES LOCKED NO ACCESS |
|
12/18/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. CLOSET FLANGE SHALL REST 1/4" TOP OF FLANGE FROM FINISHED FLOOR. PER 2003 UPC INSTALLATION REQUIREMENTS. 2. DISCHARGE FROM SEWER EJECTOR PUMP SHALL DISCHARGE INTO TOP OF DRAINAGE CONNECTION PER PLAN. THIS PUMP SHALL BE DUPLEX SYSTEM MEETING 2003 UPC REQUIREMENTS. |
|
10/23/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. SHALL SEE CLOSET FLANGE INSTALL PRIOR TO SETTING STOOLS. |
|
10/20/2006 | PLUMBING - INTERMEDIATE | Denied | SHALL PROVIDE PRIMER & THEN TAPE ON GAS PIPING AS REQUESTED ON 10/18/06. SHALL TEST ON PIPING TO WATER HEATER OK ONLY | |
10/18/2006 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. DRAIN & WASTE PIPING TO HAVE 1/4" PER FOOT FALL MINIMUM 3" + BELOW. 2. ALL PIPING TO BE SUPPORTED AT CORRECT INTERVALS. 3. INSTALL FLOOR DRAIN PER PLAN AND KITCHEN SINK DRAINAGE FITTINGS & PER PLAN. 4. REPAIR LEAK AT TUB DRAINAGE & TEST WASTE & VENT THRU ROOF WITH TEST ON TUBS & OVERFLOW. 5. ABANDONED WASTE & VENT TO BE REMOVED OR PERM. CAPPED. 6. GAS PIPING TO BE SCOTCHCOATED IF NOT 6" FROM FINISH GRADE OR BE PRIMED THEN TAPED 7. PROVIDE CITY APPROVED GAS ISOMETRIC FOR CSST AND ADDITION OF ROOFTOP UNITS (2) 8. NOTE: CLOSET RINGS WILL NEED TO BE SECURED TO FLOOR AND BE 1/4" ABOVE FINISH SURFACE WITH VIEWING PRIOR TO STOOL INSTALL. MAKE CORRECTIONS & RETEST ALL SYSTEMS. |