Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/27/2006 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 09/25/2006 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* APPROVAL SUBJECT TO LETTER FROM DESIGNER TO REFLECT FIELD CHANGES IN INSTALLATION. |
|
| 09/12/2006 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* PLANS NOT ON SITE. CALLED AND LEFT MESSAGE PER REQUEST. PLANS MUST REFLECT FIELD INSTALLATIONS, PLANS CALL FOR COPPER, CONTR. RAN ALUM. CONTR. ALSO NOT SIZED AS PER PLAN, INSIDE OR OUTSIDE PANELS? |
|
| 08/16/2006 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* SEE NOTES LAST INSP. |
|
| 08/11/2006 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* PLANS CALL FOR U.G SERVICE, PROVIDE REVISION APPROVED BY C.O.T |
|
| 08/07/2006 | ELECTRIC - CABLE DROP | Denied | Other homes in the area have underground service. Customer apparently went overhead prior to submitting the waiver. | |
| 08/04/2006 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* 1. YOU WILL NEED TO DETAIN A WAIVER FOR OVERHEAD ELECT. SERVICE DROP. 201 N. STONE 2. PLANS CALL FOR U.G FED SERVICE |