Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T06CM02117
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/18/2006 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 07/13/2006 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) BLOCK TRUSS BAYS, SKIP EVERY 3RD BAY 2) PARTIAL EXT. CLIP=TWO RETRO-HD'S REQUIRED AT REAR WALL, CHECK AT INTERMEDIATE INSPECTION |
|
| 07/10/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | 1) RAT RUNS AT GARAGE DROP CEILING SEE LAST INSPECTION 2) H20 DAMAGED ROOF SHEATHING 3) NO UFER |
|
| 07/05/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SHEAR BLOCKING PANELS BETWEEN TRUSSES 2) NEED LATERAL BRACING AT 3" 10 5/8" ABOVE DROP GARAGE 3) MISSING TWO P.A.'S AT REAR PATIO 4) SHIM ALL 3 PT BEARING 5) ROOF NAIL CAN'T OK UNTIL SHEAR BLK PANELS AT TRUSSES INSTALLED AND SHEAR NAIL ROOF TO DRAG TRUSSES COMPLETED |
|
| 06/26/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MISSING HD'S THROUGHOUT 2) STRAP ? ON DBL TOP PLATE WEST WALL 3) MISSING 4 X 4 POST AT GARAGE HEADER 4) NO TRUSS CALC'S ON SITE 5) SHEAR ON ROOF NOT NAILED |
|
| 06/25/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |