Permit: T06CM02095

Parcel: 13711425D


Addresses:

1720 W IRVINGTON RD

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
11/20/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
11/03/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. INSTALL CLAMP AT ICEE I BACKFLOW DEVICE.
2. PROVIDE VIEWING OF VENT FROM HAND SINK WITH CORRECT SUPPORTS ON HORIZONTAL VENT PIPING (4')
3. SUPPORT 3/4 CW PEX PIPING AT CORRECT INTERVALS
OVERHEAD & AT RISER BY FILTER.
(13) BACKFLOW CERTIFICATIONS ON SITE
4. PROVIDE NON-COPPER OR BRASS CONNECTION DOWNSTREAM OF CARBONATOR BACKFLOW.
5. PROVIDE CORRECT CLAMPS FOR BARB FITTINGS TO 3/8 WATER TUBING.