Permit: T06CM02095

Parcel: 13711425D


Addresses:

1720 W IRVINGTON RD

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
11/03/2006 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
05/02/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
PROVIDE SEALANT AT HAND SINK TO COUNTERTOP CONNECTION.
SUPPORT OVERHEAD HORIZONTAL PLASTIC VENT AT EVERY 4'
SUPPORT PVC AND ABS INDIRECT WASTE PIPING AT FLOOR SINK.
REMOVE SHARP EDGES FROM UNISTRUT.
PEX TUBING SHALL HAVE CLAMPS THAT ARE DESIGNED FOR USE W/PEX. COPPER TWO CLAMPS ARE NOT INTENDED FOR USE W/PEX.
EACH ICEMAKER AND NON-CARBONATED BEVERAGE DISPENSER SHALL HAVE A SEPARATE DOUBLE CHECK BACKFLOW PREVENTION ASSEMBLY.
WATER SUPPLY TUBING SHALL NOT BE CONNECTED TO THE TEST VALVES ON THE BACKFLOW ASSEMBLY.