Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/07/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 08/31/2006 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* - BACKFLOW CERTS RECEIVED - MAKE CLEAN OUTS WATER AND GAS TIGHT W/APPROVED THREAD SEALANT. - PERM CAP OR REMOVE SANTEE ON HS TRAP ARM. |
|
| 08/04/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* - HAND SINK IS NOT VENTED AND DRAIN LINE IS CONNECTED. - TO VENT OF F.S THIS IS AN UNSANITARY CONDITION. ALSO, THERE IS AN OPEN INDIRECT PIPE STUBBED OUT BELOW HS. - CAP HAND SINK DRAIN UNTIL CORRECTED. - SUPPORT WATER PIPING AT HS - YOU HAVE 13 BACKFLOW DEVICES BUT ONLY 12 CERTIFICATION REPORTS. - CONNECTION FROM DRAIN HOSE TO PVC SHALL BE RIGID. ALSO, YOU HAVE A LEAK. MAKE ALL CLEANOUT WATER TIGHT. - SUPPORT 3/4 CONDENSATE DRAIN AT EVERY 4' |