Permit: T06CM02094

Parcel: 112032850

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
09/07/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
08/31/2006 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
- BACKFLOW CERTS RECEIVED
- MAKE CLEAN OUTS WATER AND GAS TIGHT W/APPROVED THREAD SEALANT.
- PERM CAP OR REMOVE SANTEE ON HS TRAP ARM.
08/04/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
- HAND SINK IS NOT VENTED AND DRAIN LINE IS CONNECTED.
- TO VENT OF F.S THIS IS AN UNSANITARY CONDITION. ALSO, THERE IS AN OPEN INDIRECT PIPE STUBBED OUT BELOW HS.
- CAP HAND SINK DRAIN UNTIL CORRECTED.
- SUPPORT WATER PIPING AT HS
- YOU HAVE 13 BACKFLOW DEVICES BUT ONLY 12 CERTIFICATION REPORTS.
- CONNECTION FROM DRAIN HOSE TO PVC SHALL BE RIGID.
ALSO, YOU HAVE A LEAK. MAKE ALL CLEANOUT WATER TIGHT.
- SUPPORT 3/4 CONDENSATE DRAIN AT EVERY 4'