Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE RELOCATION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/15/2006 | ELECTRIC - SERVICE RELOCATION | Approved | ||
| 06/02/2006 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection : The service is not per code.| 210* 1. BOND SERVICE RACEWAY TO NEW DISCONNECT WITH PROPER SIZE CONDUCTOR NEC 250.66 2. BOND EXISTING GROUNDING ELECTRODES TOGETHER 250.58 CALL WHEN CHANGEOVER IS COMPLETE. |
|
| 05/31/2006 | ELECTRIC - SERVICE RELOCATION | Not ready for Inspection | IVRS - Inspection :* |