Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T06CM02092
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/31/2007 | ELECTRIC - CABLE DROP | Approved | ||
02/13/2007 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* 1) IDENTIFY SERVICE DISCONNECT 2) SECURE TOP OF METER BASE TO STRUCTURE 3) ENSURE GROUND PATH ON RACEWAYS-NEC 250.97 |
|
02/06/2007 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) THE SERVICE RACEWAY FOR "HP" WAS INSTALLED AND COVERED WITHOUT INSPECTION 2) WHERE IS UFER ? NO INSPECTION FOR UFER 3) POLE LIGHT RACEWAY TO J-BOX COVERED WITHOUT INSPECTION 4) SEAL OPENINIG IN TOP OF SERVICE-NEC 110.12 A 5) IDENTIFY SERVICE DISCONNECT-NEC 230.70 B 6) WIRING/GROUNDING TO POLE BASES NOT COMPLETE 7) EQUIP NOT SECURE TO WALL WITH PLASTIC ANCHORS-NEC 110.13 A 8) OPEN PANEL "HP" FOR INSPECTION 9) HOW WILL WATER/GAS BE BONDED TO SERVICE ?-NEC 250.104 10) CLOSE COVER ON L.B. AND INSTALL SEALING LOCKNUT INTO PANEL-NEC 110.12 11) HAVE SEVERAL LOOSE CONNECTIONS-TIGHTEN ALL-110.26 12) HAVE PLANS ON SITE FOR INSPECTION 13) IF CORRECTIONS NOT COMPLETE NEXT INSPECTION A FEE WILL BE CHARGED |
|
02/05/2007 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED ADDRESS LABEL ON SERVICE 2) NEED 2ND GROUND ROD 6' APART FROM 1ST 3) PLEASE FUSE 4) NEED A LOAD TO RELEASE |
|
01/31/2007 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection :* 1. HAVE EQUIPMENT OPEN FOR INSPECTION 2. WHERE IS UFER INSPECTION 3. HAVE PLANS FOR INSPECTION 4. THERE IS NO LOAD FOR SERVICE TO BE APPROVED FOR POWER? |