Permit: T06CM02092

Parcel: 10821018X


Addresses:

4291 N CAMPBELL AV


Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T06CM02092

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
05/31/2007 ELECTRIC - CABLE DROP Approved
02/13/2007 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection :*
1) IDENTIFY SERVICE DISCONNECT
2) SECURE TOP OF METER BASE TO STRUCTURE
3) ENSURE GROUND PATH ON RACEWAYS-NEC 250.97
02/06/2007 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) THE SERVICE RACEWAY FOR "HP" WAS INSTALLED AND COVERED WITHOUT INSPECTION
2) WHERE IS UFER ? NO INSPECTION FOR UFER
3) POLE LIGHT RACEWAY TO J-BOX COVERED WITHOUT INSPECTION
4) SEAL OPENINIG IN TOP OF SERVICE-NEC 110.12 A
5) IDENTIFY SERVICE DISCONNECT-NEC 230.70 B
6) WIRING/GROUNDING TO POLE BASES NOT COMPLETE
7) EQUIP NOT SECURE TO WALL WITH PLASTIC ANCHORS-NEC 110.13 A
8) OPEN PANEL "HP" FOR INSPECTION
9) HOW WILL WATER/GAS BE BONDED TO SERVICE ?-NEC 250.104
10) CLOSE COVER ON L.B. AND INSTALL SEALING LOCKNUT INTO PANEL-NEC 110.12
11) HAVE SEVERAL LOOSE CONNECTIONS-TIGHTEN ALL-110.26
12) HAVE PLANS ON SITE FOR INSPECTION
13) IF CORRECTIONS NOT COMPLETE NEXT INSPECTION A FEE WILL BE CHARGED
02/05/2007 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED ADDRESS LABEL ON SERVICE
2) NEED 2ND GROUND ROD 6' APART FROM 1ST
3) PLEASE FUSE
4) NEED A LOAD TO RELEASE
01/31/2007 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection :*
1. HAVE EQUIPMENT OPEN FOR INSPECTION
2. WHERE IS UFER INSPECTION
3. HAVE PLANS FOR INSPECTION
4. THERE IS NO LOAD FOR SERVICE TO BE APPROVED FOR POWER?