Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/31/2007 | ELECTRIC - UNDERGROUND | Approved | ||
| 12/14/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
| 08/15/2006 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* USE PROPER COUPLINGS AND PIPE FOR SERVICE RACEWAY CAN'T USE PLUMBING PIPE. ALSO, INSTALL WARNING RIBBON MINIMUM 12" ABOVE RACEWAYS ALL ALONG DITCH. OK TO COVER DITCH AFTER CORRECTIONS MADE. |
|
| 08/10/2006 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* SERVICE SECONDARY INSPECTION 1. EXPOSE RACEWAYS FOR INSPECTION 2. PROVIDE LISTING INFORMATION FOR RACEWAY USED, OR USE APPROVED RACEWAYS. |