Permit: T06CM02092

Parcel: 10821018X


Addresses:

4291 N CAMPBELL AV


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T06CM02092

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
05/31/2007 ELECTRIC - UNDERGROUND Approved
12/14/2006 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
08/15/2006 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
USE PROPER COUPLINGS AND PIPE FOR SERVICE RACEWAY CAN'T USE PLUMBING PIPE.
ALSO, INSTALL WARNING RIBBON MINIMUM 12" ABOVE RACEWAYS ALL ALONG DITCH.
OK TO COVER DITCH AFTER CORRECTIONS MADE.
08/10/2006 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
SERVICE SECONDARY INSPECTION
1. EXPOSE RACEWAYS FOR INSPECTION
2. PROVIDE LISTING INFORMATION FOR RACEWAY USED, OR USE APPROVED RACEWAYS.