Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM02091
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/04/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
03/25/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK POWER, CALL FOR FINAL WHEN ENERGIZED-WILL NEED A PERMANENT PANEL DIRECTORY AND INSTALL LIGHT BULB |
|
03/21/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* GO THROUGH WORK 14 GA NOT ALLOWED ON 20 AMP CKT MIN. #12 GROUND 20 AMP CKT MULTIPLE LOOSE CONNECTIONS |
|
03/19/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CORRECTIONS NOT COMPLETED, AND NOT PROPERLY DONE 2. NEED TO PAY REINSPECTION FEE 3. WORK TO BE DONE BY QUALIFIED ELECTRICIAN |
|
03/17/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
03/10/2008 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* GATE CODE #1024 OK TO DRYWALL CEILING POWER WILL NOT BE TURNED ON BEFORE COMPLETE NEED SERVICE DISCONNECT (BREAKER) AT SERVICE FINISH ALL MAKE UP AND TRIM LEAVE A CONTACT # WHEN YOU CALL |
|
04/14/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK TO COVER ELECTRICAL IN CEILING. |