Permit: T06CM02091

Parcel: 11615194B

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM02091

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
04/04/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
03/25/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK POWER, CALL FOR FINAL WHEN ENERGIZED-WILL NEED A PERMANENT PANEL DIRECTORY AND INSTALL LIGHT BULB
03/21/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
GO THROUGH WORK
14 GA NOT ALLOWED ON 20 AMP CKT
MIN. #12 GROUND 20 AMP CKT
MULTIPLE LOOSE CONNECTIONS
03/19/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CORRECTIONS NOT COMPLETED, AND NOT PROPERLY DONE
2. NEED TO PAY REINSPECTION FEE
3. WORK TO BE DONE BY QUALIFIED ELECTRICIAN
03/17/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
03/10/2008 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
GATE CODE #1024
OK TO DRYWALL CEILING
POWER WILL NOT BE TURNED ON BEFORE COMPLETE
NEED SERVICE DISCONNECT (BREAKER) AT SERVICE
FINISH ALL MAKE UP AND TRIM
LEAVE A CONTACT # WHEN YOU CALL
04/14/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER ELECTRICAL IN CEILING.