Permit: T06CM02090

Parcel: 120090570

Inspection Status: Not ready for Inspection

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
11/28/2006 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
NOTE:
1. PROVIDE OPENINGS, PERMANENT OPENINGS ONCE COMMENCING WITHIN 12" OF THE TOP AND ONE COMMENCING WITHIN 12" OF THE BOTTOM OF ENCLOSURE.
2. PROVIDE ACCESSIBLE SHUT OFF VALVE.
3. PROVIDE 3FT. MIN. TERMINATION MORE THAN 10FT. FROM RIDGE.
4. PROVIDE ROOF JACK ON BOILER AND HEATER AND APPROVED CAP.
11/21/2006 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1. PROVIDE DOUBLE WALL FLUE PIPING FOR WATER HEATER.
2. PROVIDE 1" ROUND FLUE PIPING FOR FURNACE.