Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/28/2006 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* NOTE: 1. PROVIDE OPENINGS, PERMANENT OPENINGS ONCE COMMENCING WITHIN 12" OF THE TOP AND ONE COMMENCING WITHIN 12" OF THE BOTTOM OF ENCLOSURE. 2. PROVIDE ACCESSIBLE SHUT OFF VALVE. 3. PROVIDE 3FT. MIN. TERMINATION MORE THAN 10FT. FROM RIDGE. 4. PROVIDE ROOF JACK ON BOILER AND HEATER AND APPROVED CAP. |
|
| 11/21/2006 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE DOUBLE WALL FLUE PIPING FOR WATER HEATER. 2. PROVIDE 1" ROUND FLUE PIPING FOR FURNACE. |