Inspection History Details
Inspection Status: Denied
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/01/2006 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EXTERIOR MECHANICAL ROOM HAS BEEN BUILT WITHOUT PERMITS AND IS STRUCTURALLY UNSOUND. 2. ROOF IS NOT WATER TIGHT. 3. FLOOR DOES NOT PROVIDE ADEQUATE SUPPORT FOR WH AND FURNACE. 4. THERE ARE NO COMBUSTION AIR OPENINGS. 5. MINIMUM CLEARANCES IN FRONT OF FURNACE NOT PROVIDED. 6. ELECTRICAL WIRING REQUIRES INSPECTION. 7. GAS PIPING UNDERSIZED 1" SHALL EXTEND TO FURNACE/WH LOCATION. 8. SEDIMENT TRAPS REQUIRED. T&P SHALL TERMINATE OUTSIDE. 9. REMOVE OLD WALL FURNACE FLUE WHICH HAS BEEN CONCEALED IN WALL. 10. OBTAIN STRUCTURAL, MECHANICAL, ELECTRICAL PERMITS FOR NEW MECHANICAL ROOM. |
|
| 11/28/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE TAPE & PRIMER ON FITTING AND TOOL MARKS UNDERGROUND. 2. PROVIDE FLUE PIPE AND CAP FOR WATER HEATER. |
|
| 11/21/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. PROVIDE TAPE & PRIMER ON FITTINGS AND TOLL MARKS ON UNDERGROUND GAS PIPING. 2. PROVIDE (0-15) NOT 100 TO 300 PRESSURE TEST. 3. COMPLETE LIST FROM 7/12/06 |