Inspection Status: Denied
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/01/2006 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 11/28/2006 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* | |
| 11/21/2006 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* | |
| 07/12/2006 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | 1. BLACK IRON PIPE MAY NOT BE INSTALLED UNDERGROUND. 2. PIPE TO BE TAPED PASSING THRU EXTERIOR WALL PENETRATION TO BE SEALED. 3. CONNECT ALL APPLIANCES HOOK UP ALL EQUIPMENT 4. VENT OPENINGS WITHIN TEN FEET OF AIR INTAKE TO BE RAISED. 5. REQUIRE TEN POUND TEST ON ENTIRE SYSTEM. GAS PIPE INFORMATION 201 N STONE CITY OF TUCSON GAS PIPE HANDOUT |