Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/26/2008 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 03/21/2008 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED MIN. 90 AMP BREAKER FOR OVER CURRENT PROTECTION SUB PANEL FEEDER 2) RUN A #8 CU. GRD WIRE FOR CLEARANCE FEEDER 3) SEPERATE NEUTRALS AND GRDS IN SUB PANEL, AT BUSS BARS NEUTRAL/GRD 4) NEED ROMEX CONNECTION AT SUB/PANEL CIRCUITS ENTRY, PLUG LARGE HOLE AT PANEL BOTTOM 5) PROTECT ROMEX TO 8'-0" HT. 6) NEED 1/2" MIN SHEETROCK SEPERATION HOUSE TO GARAGE |