Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/14/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/08/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. (1) OUTDOOR WALL PACK NOT OPERATING 2. ROOFTOP RECEPTACLE NOT GFI PROTECTED 3. REPLACE BAD DISCONNECT ON ROOF |
|
| 11/07/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. UNIT LOCKED NO ACCESS 2. PLEASE REMOVE CEILING TILES FOR CEILING INSPECTION 3. PLEASE OPEN JUNCTION BOXES & PANELS & HAVE ELECTRICAL CONTRACTOR ON SITE |
|
| 10/29/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. VERIFY INTERMEDIATE INSPECTION 2. OPEN CEILING FOR INSPECTION 3. LABEL DISCONNECTING MEANS 4. PANEL SCHEDULES TO BE AS PER 408.4 - NO ABBREVIATIONS 5. RECEPTACLE COVERS TO BE AS PER 406.8 6. IDENTIFY COOLER DISCONNECTS & AC DISCONNECT 7. AC LOCKNUTS INSTALLED BACKWARDS 8. SUPPORT CONDUIT TO LIGHT & TIGHTEN FITTING |
|
| 10/25/2007 | ELECTRIC - FINAL | Partial Approval | ||
| 10/10/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* SERVICE INSPECTION ONLY |
|
| 10/03/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SECONDARY RACEWAYS FROM TEP XFMR TO SES WAS NEVER INSPECTED - NEED TO EXPOSE. 2. INSTALL MAIN BONDING JUMPER AT SERVICE DISCONNECT NEC 250.28 3. MARK "SERVICE DISCONNECT" NEC 230.20 4. BOND GROUNDING ELECTRODE CONDUCTOR TO BOTH ENDS OF 3/4" EMT NEC 250.64(E) 5. GROUNDING ELECTRODE CONDUCTOR TAP TO BE SIZED PER NEC 250.30(A)(5) 6. BONDING JUMPER TO BE SIZED PER NEC 250.102 & 250.66 7. SERVICE INSPECTION ONLY 8. BOND WATER PIPE TO SERVICE PER NEC 250.104 |