Permit: T06CM02069

Parcel: 141185520


Addresses:

9367 E OLD VAIL RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/14/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
11/08/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. (1) OUTDOOR WALL PACK NOT OPERATING
2. ROOFTOP RECEPTACLE NOT GFI PROTECTED
3. REPLACE BAD DISCONNECT ON ROOF
11/07/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. UNIT LOCKED NO ACCESS
2. PLEASE REMOVE CEILING TILES FOR CEILING INSPECTION
3. PLEASE OPEN JUNCTION BOXES & PANELS & HAVE ELECTRICAL CONTRACTOR ON SITE
10/29/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. VERIFY INTERMEDIATE INSPECTION
2. OPEN CEILING FOR INSPECTION
3. LABEL DISCONNECTING MEANS
4. PANEL SCHEDULES TO BE AS PER 408.4 -
NO ABBREVIATIONS
5. RECEPTACLE COVERS TO BE AS PER 406.8
6. IDENTIFY COOLER DISCONNECTS & AC DISCONNECT
7. AC LOCKNUTS INSTALLED BACKWARDS
8. SUPPORT CONDUIT TO LIGHT & TIGHTEN FITTING
10/25/2007 ELECTRIC - FINAL Partial Approval
10/10/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
SERVICE INSPECTION ONLY
10/03/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SECONDARY RACEWAYS FROM TEP XFMR TO SES WAS NEVER INSPECTED - NEED TO EXPOSE.
2. INSTALL MAIN BONDING JUMPER AT SERVICE DISCONNECT NEC 250.28
3. MARK "SERVICE DISCONNECT" NEC 230.20
4. BOND GROUNDING ELECTRODE CONDUCTOR TO BOTH ENDS OF 3/4" EMT NEC 250.64(E)
5. GROUNDING ELECTRODE CONDUCTOR TAP TO BE SIZED PER NEC 250.30(A)(5)
6. BONDING JUMPER TO BE SIZED PER NEC 250.102 & 250.66
7. SERVICE INSPECTION ONLY
8. BOND WATER PIPE TO SERVICE PER NEC 250.104