Permit: T06CM02060

Parcel: 112081030


Addresses:

2904 E CANNES ST


Inspection Status: Not ready for Inspection

Inspection History: PLUMBING - FINAL

Permit Number - T06CM02060

Inspection Description - PLUMBING - FINAL

Inspection Status - Not ready for Inspection

Date Description Inspector Results Comments
08/28/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
PLAN CALLS FOR A FLOOR DRAIN
INSTALLED IS A BELL REDUCER
SEE NOTES FROM 08 2007
08/28/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
IT HAS BEEN AGREED THAT DUE TO THE METHANE BARRIER REQUIREMENTS, AN FHA FLOOR DRAIN AND TRAP PRIMER IS IMPRACTICAL. A HUB DRAIN WITH STRAINER WILL BE ACCEPTED ON THIS JOBSITE.
08/20/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) DRAIN IN MECHANICAL ROOM NOT ON THE PLAN
2) A FITTING IS NOT AN APPROVED INDIRECT WASTE RECEPTACLE
3) INDIRECT WASTE PIPING NOT PER PLAN
08/17/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
TEST REQUIRED AFTER CONCEALMENT OF GAS PIPING
REMOVE TRAP ON SOFTENER DRAIN
LABEL ELECTRICAL PANEL
WATER HAMMER ARRESTORS REQUIRED AT WASHER BOX
WATER HEATER NOT PER DETAIL 203