Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM02060
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/20/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
08/17/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ROOF GFI HAS NO POWER 2. GROUND ELEVATOR DISCONNECTS AND ENCLOSURES ROMEX NEEDS CONNECTORS, SEAL UNUSED OPENINGS 3. MAX 40 WATTS IN SHOWER TRIMS 4. PROVIDE GFI PROTECTION FOR RECEPTACLE IN HWT ROOM 5. PROVIDE ARC FAULT PROTECTION PER NEC 210.12 6. CHECK PANEL DIRECTORIES |