Permit: T06CM02060

Parcel: 112081030


Addresses:

2904 E CANNES ST


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM02060

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
03/07/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
NOTE: DISPOSAL SWITCH BOX OVERFILLED BY ONE CONDUCTOR.
03/05/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) EQUIPMENT GROUNDS TO BE TWISTED TOGETHER-THEN CRIMPED
2) LAUNDRY RECEPTACLE HANGING
3) IDENTIFY WHITE USED AS HOT
4) KITCHEN 2 GANG OVER FILLED ?
5) NEED NAIL PLATES-KITCHEN SWITCH-OTHER AREAS
6) TIGHTEN GAS BOND
03/02/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
01/02/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER COMMON WALLS
12/28/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
INSPECTION FOR COMMON WALL ONLY
1) NAIL NOT ALLOWED IN BOXES-NEC 314.23 B1
2) NAIL PLATE AS NEEDED-NEC 300.4