Permit: T06CM01990

Parcel: 141331890


Addresses:

8345 S MINOAN DR


Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T06CM01990

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
08/22/2006 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
08/21/2006 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) REPLACE BROKEN SILL PLATES ON COLUMNS
2) HOUSE OK-NOT COLUMNS
08/17/2006 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) MAIN HOUSE OK
2) REAP COLUMN PLATES AND STRAPS
08/15/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REAR COLUMNS NOT BOLTED TO CONCRETE, NOT STRAPED TO BEAM
2) MISSING LTP 4'S SHEAR TO BOTTOM CHORD
3) FRONT SHEAR AT GARAGE ABOVE HEADER NOT NAILED
4) 1ST AND 2ND FLOOR STRAPS TO BE MAX 4'-0" ON CENTER
5) COIL STRAPS AT STAIR SHEAR
6) FLOOR IS NOT NAILED
7) HANGERS MISSING FRONT PORCH