Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - OUTDOOR LIGHTING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/19/2007 | ELECTRIC - OUTDOOR LIGHTING | Approved | IVRS - Inspection :* | |
| 01/17/2007 | ELECTRIC - OUTDOOR LIGHTING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. DISCONNECT FOR COMPRESSOR IS BLOCKED BY COMPRESSOR 2. FLEX TO COMPRESSOR NEEDS TO BE STRAPPED AT EACH END WITHIN 12' OF TERMINATIONS. 3. IDENTIFY PANEL DIRECTORY 4. IN USE COVER FOR EXTERIOR GFI NOT PROPERLY MOUNTED 5. INTERIOR/EXTERIOR/EMERGENCY LIGHTING NOT WORKING |