Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/19/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 01/11/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) INSPECTION FOR SERVICE ONLY |
|
| 12/04/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK WALL COVER COMPRESSED AIR BOND? |
|
| 11/22/2006 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) BOND SPRINKLER, GAS AND WATER PIPES TO PANEL-NEC 250.104 AND COMPRESSED AIR 2) STRAP EMT WITHIN 3' OF BOXES 3) INSTALL K.O. BLANKS AND MUD RINGS ARE NEEDED |
|
| 11/21/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* WORK IN PROGRESS |