Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T06CM01977

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
12/08/2006 EXT METAL CLIPS/EXT SHEATHING Approved
08/07/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED PAGE 5-7
2) MISSING HIP HANGERS 1ST AND 2ND FLOOR
3) INCORRECT NAILS IN HANGERS
4) MORE NAILS NEEDED IN LEDGERS 4-16D
5) MISSED REAR SHEAR WALL WITH P.A.
6) NEED WIND BRACE 1ST FLOOR S/W SIDE
7) 2 NAILS IN EACH WIND BRACE AT PLATES
8) MISSING GARAGE INTERIOR POST
9) NEED 1ST TO 2ND FLOOR STRAPS ON PERIMETER 48" ON CENTER
10) DBL STUDS UNDER GIRDER