Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T06CM01971
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/11/2006 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
| 07/14/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CONNECT ALL 1ST AND 2ND FLOOR COIL STRAPS (4 NAILS ?) INTO TOP/BOT PLATES 2) TIE WALL SHEAR TO TOP CHORD 3) NAIL ALL 2ND FLOOR PLATES AT 12" ON CENTER 16D'S 4) SUPPORT UNDER LOAD PT, BETWEEN FLOORS NEXT TO STAIR 5) WRONG NAILS IN HANGERS AT LIVING ROOM, HANGER SIZE NOT ON PLAN 6) USE CORRECT NAILS IN P.A.'S, STHD P. ? SHEAR5 HAS BEEN CUT 7) FRONT TEM TO SHORT-NO BEARING 8) WALKING DECK NOT INSTALLED |