Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T06CM01948
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/18/2006 | EXT METAL CLIPS/EXT SHEATHING | Approved | IVRS - Inspection :* | |
09/11/2006 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | 1) (PAHD 22) USE 16D SINKERS 0.148 DIAMETER X 3 1/4" LONG 2) EXTEND 2ND FLOOR SHEAR TO OUTSIDE OF SECOND FLOOR WALL |
|
09/08/2006 | EXT METAL CLIPS/EXT SHEATHING | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED BY SUPER |
|
08/31/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. FRONT ENTRY ROOF MISSING STRAPS HANGER 2. LONG DRAG STRAPS AT WINDOWS 3. 1ST 2ND FUN STRAPS MIN. NAILS PER FLR 4. MAG STRAPS NOT NAILED 5. STUDS UNDER GW GARAGE 6. COL. TO BEAM ENTRY NEEDS HANGER 7. WIND BRACES NOT INSTALLED 8. REAR PORCH COLS BEAM TO CONCRETE 9. REAR 1ST 2ND FLR. STRAPS 10. REAR P.A'S NOT NAILED 11. MISSING HANGER PORCH FACIA REAR 12. SHEAR TRANSFERS 2ND FLR 13. MISSING NAILS IN HANGERS FLR TRUSSES 14. "C" EW INTERSECTING WALL WEST 15. HPAD IS NOT SECURED 16. MISSING TWO 4' PANELS SHEAR REAR 1ST 2ND 17. 4' LINE NOT NAILED ROOF 18. FRONT ROOF HIP DCEL BACKING ENTRY AREA 19. FUR. NOT NAILED NOT STRAPPED 20. FRIEZE BOARDS NOT NAILED 21. NAIL ALL 2ND FLR PLATES 6"-12" 22. DBL STUDS UNDER GIRDERS & BEAMS |