Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
Permit Number - T06CM01929
Inspection Description - BUILDING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/12/2007 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
03/08/2007 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NEED VISABLE ADDRESS (R.321.1) 2) SEAL PENETRATIONS IN FIREWALL OF GARAGE, (WIRE, DOOR BELL TRANSFORMER, HOT WATER HEATER PRV) 3) OVER TORQUED SCREWS IN PANEL AT LUGS 4) SNAP OFF SET SCREW ON VACUUM BREAKER ON HOSE BIB 5) PUT SPARK SHIELD IN FRONT OF VENTS OF FURNACE IF NEEDED PER MFG. SPECS |