Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T06CM01929
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/21/2006 | FRAMING | Approved | IVRS - Inspection :* | |
12/18/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* FIREBLOCKING IN CHASE WHERE OVERCUT 2ND FLOOR |
|
12/11/2006 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED PER SUPER |
|
12/06/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SHIM ALL LET-INS EXT. WALL 2) WHERE STUDS HAVE BEEN NOTCHED MORE THAN 1/2-ANY WALL REPLACE STUD 3) FIREBLOCKING AT 10' BALLOON WALL 4) CUT WIRE (12-2) NORTHWALL KITCHEN 5) STOPPED INSPECTION-CORRECTIONS HAVE NOT BEEN MADE |
|
11/29/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) TIGHTEN RED HEADS 2) FIRE BLOCK DUCT IN CHASE FLOOR AND CEILING WHERE OSB OVER CUT 3) SHIM ALL LET INS COMPLETELY 4) CUT WIRE (12-2) NORTH WALL KITCHEN 5) SECONDARY A/C DRAIN NEEDS TO GO TO OBVIOUS LOCATION 6) FURNACE NEEDS SINGLE WALL CONNECTOR PIPE BEFORE B-VENT |
|
11/20/2006 | FRAMING | Not ready for Inspection | IVRS - Inspection :* |