Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T06CM01925
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/17/2006 | FRAMING | Approved | IVRS - Inspection :* | |
08/16/2006 | FRAMING | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) WRONG ADDRESS-SHOULD BE 64XX 2) NO PRIOR INSPECTION REPORT ON SITE 3) HOUSE INSULATED WITHOUT APPROVAL-REMOVE INSULATION 4) RED HEADS LOOSE 5) GAS BOND CLAMP MUST BE EXPOSED-CANNOT BE ENCLOSED IN WALL 6) ITEMS 1, 2, 3, 4 OR 5/D3 NOT COMPLIED WITH AT SHEARWALL TOP PLATES 7) STOPPED INSPECTION |
|
08/10/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WRONG ADDRESS 2) NO LATH 3) RED HEADS LOOSE 4) BLOCK DUCT BOOTS 5) NO GAS BOND 6) ANCHOR WALLS TOP PLATES |