Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/17/2007 | FRAMING | Approved | IVRS - Inspection :* | |
| 01/12/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) VACUUM BREAKER ON HOSE BIB 2) LOW COMBUSTION AIR GRILL NEEDED IN GARAGE 3) SOLID BLOCKING NEEDED BETWEEN JOISTS ON EITHER SIDE OF FURN. FLUE IN GARAGE 4) CHECK FIREBLOCKING AT DRIP CEILINGS THROUGHOUT 5) BANG PLATES ON ELECTRICAL AT TOP PLATES 6) REPLACE ALL BLOWN FIRE BLOCKS 7) FIRESTOP HOLES THROUGH FIREBLOCKS IN KITCHEN 8) ANCHOR BOLTS MISSING THROUGHOUT 9) SEAL VAPOR BARRIER AT LOW VOLTAGE PENETRATION 10) COMPLETE HANGER NAILS AT HIP JACK-MASTER BATH 11) STOPPED INSPECTION |
|
| 12/04/2006 | FRAMING | Not ready for Inspection | IVRS - Inspection :* |