Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
09/06/2006 FRAMING Approved
07/24/2006 FRAMING Partial Approval IVRS - Inspection :*
1) HAVE TRUSS REPAIR APPROVED BY CITY OF TUCSON
07/18/2006 FRAMING Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspection
Garage shearwall 2 requires anchor bolts at 6' on center and clipped to floor trusses with a35 clips per 6sd3
F5 truss is not bearing at mid point bearing location per truss drawings-Provide City of Tucson approved engineering repair
Pay reinspection fee prior to next inspection
07/17/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) ITEMS 3, 4 AND 6 OF 7/14/06 INSPECTION NOT COMPLIED WITH
07/14/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LATHE NOT COMPLETE
2) TRUSS BLOCKING NOT PER 7/SD4 MUST BEAR ON DBL TOP PLATE AND A35 CLIP
3) NO DWV WATER TEST
4) 6/SD3 NOT COMPLIED WITH ON GARAGE #2 SHEARWALL
5) TOP OF STAIR STRINGERS MUST BEAR ON SOMETHING. PROVIDE APPROVED DETAIL
6) TRYSS F5 MID POINT BEARING NOT LOCATED OVER WALL. PROVIDE ENGINEER APPROVED CITY APPROVED REPAIR