Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/06/2006 | FRAMING | Approved | ||
| 07/24/2006 | FRAMING | Partial Approval | IVRS - Inspection :* 1) HAVE TRUSS REPAIR APPROVED BY CITY OF TUCSON |
|
| 07/18/2006 | FRAMING | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspection Garage shearwall 2 requires anchor bolts at 6' on center and clipped to floor trusses with a35 clips per 6sd3 F5 truss is not bearing at mid point bearing location per truss drawings-Provide City of Tucson approved engineering repair Pay reinspection fee prior to next inspection |
|
| 07/17/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ITEMS 3, 4 AND 6 OF 7/14/06 INSPECTION NOT COMPLIED WITH |
|
| 07/14/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) LATHE NOT COMPLETE 2) TRUSS BLOCKING NOT PER 7/SD4 MUST BEAR ON DBL TOP PLATE AND A35 CLIP 3) NO DWV WATER TEST 4) 6/SD3 NOT COMPLIED WITH ON GARAGE #2 SHEARWALL 5) TOP OF STAIR STRINGERS MUST BEAR ON SOMETHING. PROVIDE APPROVED DETAIL 6) TRYSS F5 MID POINT BEARING NOT LOCATED OVER WALL. PROVIDE ENGINEER APPROVED CITY APPROVED REPAIR |