Permit: T06CM01898

Parcel: 140264830

Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T06CM01898

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
08/15/2006 FRAMING Approved IVRS - Inspection :*
08/14/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) REMOVE INSULATION-
2) COMPLETE ALL ITEMS FROM 8/7/06 INSPECTION. 3) INTERMEDIATES HAVE NOT BEEN APPROVED
08/08/2006 FRAMING Not ready for Inspection IVRS - Inspection :*
08/07/2006 FRAMING Partial Approval IVRS - Inspection :*
1) HANGERS MISSING GARAGE HIP TRUSSES
2) PENDING STUCCO MESH
3) NAIL STOPS 1 1/2 VENT MASTER BEDROOM
4) SUPPLY TEST OK
5) NO DWV TEST
6) REROUTE WATER HEATER B-VENT, MINIMUM 30 DEGREE SLOPE
7) COMPLETE STUCCO MESH