Permit: T06CM01891

Parcel: 12402047B


Addresses:

1627 E 1ST ST #1101

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
09/30/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
CORRECTIONS MADE OK
OK TO COVER ALL AREAS
09/26/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
ONE UNIT INSPECTED
1. ABS TO BE SUPPORTED AT EACH CHANGE OF DIRECTION OR ELEVATION AND AT THE END OF BRANCHES, THEN NO MORE THAN FOUR FEET BETWEEN HANGERS. PLUMBERS TAPE NOT APPROVED STRAP. WOOD SHIMS NOT APPROVED.
2. ABS LEAKS
09/21/2007 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
UNIT 1 INSPECTED
PROTECT CO PASSING THROUG STUCCO
NO TEST ON DWV
AAV NOT SHOWN ON PLAN
TRAP ARM CANNOT CHANGE ELEVATION
NO PLUMBERS TAPE
SUPPORT HORIZ. ABS
TRAP ARM CANNOT CHANGE SIZE