Permit: T06CM01891

Parcel: 12402047B


Addresses:

1627 E 1ST ST #1101

Inspection Status: Not Applicable

Inspection History: ELECTRIC - UFER

Date Description Inspector Results Comments
03/26/2008 ELECTRIC - UFER Not Applicable IVRS - Inspection :*
01/22/2008 ELECTRIC - UFER Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GROUNDING ELECTRODE CONDUCTOR TO TERMINATE ON NEUTRAL BUS
2. PROPERLY INSTALL BONDING JUMPER FROM SERVICE RISER
3. INSTALL MAIN BONDING JUMPER
4. SEAL OPENINGS WHERE WIRES ENTER WITH
NON-COMBUSTIBLE SEALANT
5. GROUND RODS OK
6. SECURE GROUNDING ELECTRODE CONDUCTOR TO BUILDING SURFACE
7. WIRE NUT WIRES FOR VANITY LIGHTS
01/17/2008 ELECTRIC - UFER Denied IVRS - Inspection :
Install ufer ground shown on plans.| 225*
STRUCTURE BUILT BEFORE UFER INSTALLED/INSPECTED
01/14/2008 ELECTRIC - UFER Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. GROUND RODS TO BE MINIMUM 6' APART
2. SERVICE TO BE OPEN AND ACCESSIBLE FOR INSPECTION
3. UFER NOT INSTALLED
4. NO OPEN WIRING/TRIM OUT UNITS FOR POWER APPROVAL

PARTIAL INSPECTION - SERVICE NOT OPEN/ACCESSIBLE