Inspection History Details
Inspection Status: Not Applicable
Inspection History: ELECTRIC - UFER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/26/2008 | ELECTRIC - UFER | Not Applicable | IVRS - Inspection :* | |
| 01/22/2008 | ELECTRIC - UFER | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUNDING ELECTRODE CONDUCTOR TO TERMINATE ON NEUTRAL BUS 2. PROPERLY INSTALL BONDING JUMPER FROM SERVICE RISER 3. INSTALL MAIN BONDING JUMPER 4. SEAL OPENINGS WHERE WIRES ENTER WITH NON-COMBUSTIBLE SEALANT 5. GROUND RODS OK 6. SECURE GROUNDING ELECTRODE CONDUCTOR TO BUILDING SURFACE 7. WIRE NUT WIRES FOR VANITY LIGHTS |
|
| 01/17/2008 | ELECTRIC - UFER | Denied | IVRS - Inspection : Install ufer ground shown on plans.| 225* STRUCTURE BUILT BEFORE UFER INSTALLED/INSPECTED |
|
| 01/14/2008 | ELECTRIC - UFER | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. GROUND RODS TO BE MINIMUM 6' APART 2. SERVICE TO BE OPEN AND ACCESSIBLE FOR INSPECTION 3. UFER NOT INSTALLED 4. NO OPEN WIRING/TRIM OUT UNITS FOR POWER APPROVAL PARTIAL INSPECTION - SERVICE NOT OPEN/ACCESSIBLE |