Permit: T06CM01883

Parcel: 120062080


Addresses:

4115 S 6TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - UFER

Date Description Inspector Results Comments
06/01/2007 ELECTRIC - UFER Approved IVRS - Inspection :*
WEST SPACE LOCKED, OK WALLS EXCEPT WEST SPACE
OK CEILINGS.
05/30/2007 ELECTRIC - UFER Denied IVRS - Inspection :
See detailed listing on site.| 999*
05/16/2007 ELECTRIC - UFER Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio
05/14/2007 ELECTRIC - UFER Partial Approval IVRS - Inspection :*
- 2 GROUND RODS REQUIRED 6' MIN. APART
- SEE NOTES LAST INSP. NEED APPROVED PLANS

PERMIT?
04/23/2007 ELECTRIC - UFER Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED APPROVED PLANS
2. FEEDERS & SERVICE MAINS NOT PER SITE PLAN
3. CONTR. USED #2 ALUM. FEEDERS
4. UNCOVER OR EXPOSE GROUNDING.