Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/18/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 06/28/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* OK TO FILE FOR TEMP C OF O |
|
| 06/25/2007 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 06/21/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE MIN. R-8 DUCT LINER ON EXPOSED DUCT 2. PROVIDE A ROOF JACK AT CONDENSATE DRAIN 3. PROVIDE THE 1" SPACE ON FIREPLACE DAMPER 4. PROVIDE SCREENS IN T-TOPS 5. PROVIDE PERMANENT ACCESS OUT OF ROOF WELL 6. PROVIDE A FRESH AIR INTAKE ON PACKAGE UNIT 7. EXTEND BOILER VENT 2' ABOVE PARAPET WITH AN APPROVED CAP. REPAIR ALL VENT CONNECTORS ON BOILERS AND WATER HEATER. |
|
| 02/13/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* DISCUSSED TEMP C OF O ISSUES FOR MODELS & UNIT 3124 |