Permit: T06CM01880

Parcel: 13314460A

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
05/11/2007 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
1) STILL NEED LOCKING MECHANISM ON FIREPLACE DAMPER
2) STILL NEED TO SEE WATER HEATER VENTS
3) OK FOR SHEETROCK
05/08/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
PROVIDE LOCKING DEVICE TO KEEP FIREPLACE DAMPER OPEN MIN. 1" AT ALL TIMES.
ON FINAL BE SURE TO REMOVE ABANDONED VENT PIPING FOR WATER HEATERS & BOILERS.
PROVIDE 1/4" PER FT SLOPE ON HORIZONTAL SECTION OF SINGLE WALL PIPE.
PROVIDE A CONDENSATE DRAIN
OK TO SHEETROCK 2ND FLOOR & 1ST FLOOR SOFFITS
PROVIDE EXHAUST FAN 1ST FLOOR RESTROOM AND REPAIR BROKEN EXHAUST DUCT.
02/02/2007 MECHANICAL - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) CHECKED RETURN AIR UNDER FLOOR
2) OK TO COVER