Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/10/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/28/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK TCO SUBJECT TO DETERMINATION OF S.LONG 1. WAITING ON LIGHTS |
|
| 06/25/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 06/19/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MISSING UPSTAIRS BACK PORCH LIGHT FIXTURES AND POOL ROOM AND OUTSIDE LIGHTS ALSO, AT POOL 2. GROUND FLOOR BOXES 3. EM EXIT TO BE ON AREA SERVED 700.12 4. PANEL LABELING TO BE AS PER 408.4 -- NO GENERAL LABELING 5. COVER OPEN BOXES 6. BRING EXTENDER RINGS TO SURFACE ROOF: 1. BOND JUNCTION BOXES 2. LABEL DISCONNECT 3. USE APPROVED PLUGS FOR BOXES I WILL CHECK WITH THE INSPECTIONS SUPERVISOR REGARDING POOL EQUIPMENT |
|
| 02/13/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* MET TO ANSWER QUESTIONS |