Permit: T06CM01878

Parcel: 13314460A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/10/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) OK FINAL
08/08/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. FINISH SITE LIGHTING & POWER WEST SIDE
2. SEPARATE GROUNDS & NEUTRAL AT SUB-PANEL USE CORRECT TERMINALS 8267

CHECK ROOF NEXT TIME
08/03/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. TIGHTEN FLEX CONNECTORS
2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE 314.20
3. CORRECTLY GROUND SUB-PANELS
4. FINISH