Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/27/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/24/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. MAINTAIN WORKING CLEARANCE 110.26 2. CLEAN PANEL 6251 3. PROPERLY ATTACH GROUND BAR 6251 |
|
| 08/23/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* GEORGE TO RESCHEDULE |
|
| 07/26/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 6150: FINISH DRYWALL NORTH WALLS 6249: FINISH CEILING DRYWALL 6250: FINISH DRYWALL NORTH WALLS FINISH FOUNTAIN 6153: NOT READY 6151: NOT READY OK UNITS EXCEPT AS NOTED |
|
| 07/24/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. ANTI-OXIDE COMPOUND NEEDED FOR ALL ALUMINUM CONDUCTOR 2. BREAKER TO BE LISTED FOR USE BY MANUFACTURE 110.3 3. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RINGS 314.20 4. GROUND FIXTURE HARDWARE 5. INSTALL ALL STRANDS UNDER TERMINAL LUGS 6. UNSAFE NM CABLE AT SERVICE TO CABLE BOX |
|
| 07/20/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. WATER HEATER TO HAVE A DISCONNECTING MEANS 2. LOOSE FITTING FURNACE 3. GROUND SWITCHES 4. KITCHEN GFI'S NOT WORKING |
|
| 07/18/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* UNITS NOT READY FOR INSPECTION |