Permit: T06CM01876

Parcel: 13314460A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/27/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/24/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. MAINTAIN WORKING CLEARANCE 110.26
2. CLEAN PANEL 6251
3. PROPERLY ATTACH GROUND BAR 6251
08/23/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
GEORGE TO RESCHEDULE
07/26/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
6150: FINISH DRYWALL NORTH WALLS
6249: FINISH CEILING DRYWALL
6250: FINISH DRYWALL NORTH WALLS
FINISH FOUNTAIN
6153: NOT READY
6151: NOT READY

OK UNITS EXCEPT AS NOTED
07/24/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. ANTI-OXIDE COMPOUND NEEDED FOR ALL ALUMINUM CONDUCTOR
2. BREAKER TO BE LISTED FOR USE BY MANUFACTURE 110.3
3. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RINGS 314.20
4. GROUND FIXTURE HARDWARE
5. INSTALL ALL STRANDS UNDER TERMINAL LUGS
6. UNSAFE NM CABLE AT SERVICE TO CABLE BOX
07/20/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. WATER HEATER TO HAVE A DISCONNECTING MEANS
2. LOOSE FITTING FURNACE
3. GROUND SWITCHES
4. KITCHEN GFI'S NOT WORKING
07/18/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
UNITS NOT READY FOR INSPECTION