Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/03/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* OK ROUGH |
|
| 05/02/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK 1/2 OF BUILDING 12 UNITS |
|
| 04/30/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspection Connect water bond conductors Grounds only 3/4 of a turn under screw not multi pole wraps Conductors to extend 6" outside of boxes Correctly identify ungrounded conductors Use anti-oxide compound on all aluminum conductors Protect cables crossing rafters |
|
| 04/24/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. 3/0 PANCAKE BOXES ALLOW ONLY ONE CABLE. 2. PROTECT CABLE AT EDGES 3. PREVENT FIRE SPREAD 300.21 4. EXPOSED NM CABLE OUT OF SOFFIT 5. SECURE NM CABLE TO BOXES 6. EXTEND BOXES TO EDGE OF DRYWALL 7. SUPPORT SE CABLE ON VERTICAL 8. FINISH PREVIOUS ITEMS |
|
| 04/23/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. UNCOVER AREAS COVERED WITH DRYWALL FOR INSPECTION 2. WE HAVE BOX OVERFILL 314.16 3. ONLY ONE CONDUCTOR UNDER TERMINAL SCREW 4. MAINTAIN CLEARANCE WITH CANS 5. SCREWS NOT ALLOWED IN FRONT OF BOX SIDES 314.23 6. USE APPROVED SPLICE CONNECTORS - GROUNDS 7. SUPPORT NM CABLES WITHIN 12" OF CANS, EXHAUST FANS AND BOXES 8. SHEATHING OF NM CABLES TO BE 1/4" INTO BOXES |