Permit: T06CM01876

Parcel: 13314460A

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
05/03/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
OK ROUGH
05/02/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK 1/2 OF BUILDING 12 UNITS
04/30/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspection
Connect water bond conductors
Grounds only 3/4 of a turn under screw not multi pole wraps
Conductors to extend 6" outside of boxes
Correctly identify ungrounded conductors
Use anti-oxide compound on all aluminum conductors
Protect cables crossing rafters
04/24/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. 3/0 PANCAKE BOXES ALLOW ONLY ONE CABLE.
2. PROTECT CABLE AT EDGES
3. PREVENT FIRE SPREAD 300.21
4. EXPOSED NM CABLE OUT OF SOFFIT
5. SECURE NM CABLE TO BOXES
6. EXTEND BOXES TO EDGE OF DRYWALL
7. SUPPORT SE CABLE ON VERTICAL
8. FINISH PREVIOUS ITEMS
04/23/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. UNCOVER AREAS COVERED WITH DRYWALL FOR INSPECTION
2. WE HAVE BOX OVERFILL 314.16
3. ONLY ONE CONDUCTOR UNDER TERMINAL SCREW
4. MAINTAIN CLEARANCE WITH CANS
5. SCREWS NOT ALLOWED IN FRONT OF BOX SIDES 314.23
6. USE APPROVED SPLICE CONNECTORS - GROUNDS
7. SUPPORT NM CABLES WITHIN 12" OF CANS, EXHAUST FANS AND BOXES
8. SHEATHING OF NM CABLES TO BE 1/4" INTO BOXES