Permit: T06CM01874

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/18/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/08/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
LAST ITEMS #5 & 7 OF PREVIOUS INSPECTION TO COMPLETE
06/05/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELLED
05/31/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. OPEN NEUTRAL KITCHEN 4330
2. PROPERLY GROUND FIXTURE - CORRECT SPLICES
3. W/H DISCONNECT WITHIN SITE FROM UNIT 4332
4. FOR UNIT 4129 EXTEND LANDING TO 30" FOR WORKING SPACE -- 110.26
5. FINISH OUTSIDE LANDSCAPE & LIGHTING
7. FINISH UNIT 4130
05/30/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. DISPOSAL PLUG BURIED IN DRYWALL (4125)
2. CLEAN EXCESS DIRT FROM PANELS
3. BREAKERS FOR MULTI-WIRE CIRCUITS TO SAME Y ORE TO HAVE HANDLE TIES
4. USE ALL HARDWARE TO HANG LIGHTS
5. 2 CIRCUITS TO SUPPLY KITCHEN COUNTERTOPS (4128)
6. REATTACH PANEL TO WALL & CONDUIT
7. CHECK FOR WORKING SPACE PANEL (4129)