Inspection History Details
Permit: T06CM01874
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/18/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/08/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* LAST ITEMS #5 & 7 OF PREVIOUS INSPECTION TO COMPLETE |
|
| 06/05/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CANCELLED |
|
| 05/31/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OPEN NEUTRAL KITCHEN 4330 2. PROPERLY GROUND FIXTURE - CORRECT SPLICES 3. W/H DISCONNECT WITHIN SITE FROM UNIT 4332 4. FOR UNIT 4129 EXTEND LANDING TO 30" FOR WORKING SPACE -- 110.26 5. FINISH OUTSIDE LANDSCAPE & LIGHTING 7. FINISH UNIT 4130 |
|
| 05/30/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. DISPOSAL PLUG BURIED IN DRYWALL (4125) 2. CLEAN EXCESS DIRT FROM PANELS 3. BREAKERS FOR MULTI-WIRE CIRCUITS TO SAME Y ORE TO HAVE HANDLE TIES 4. USE ALL HARDWARE TO HANG LIGHTS 5. 2 CIRCUITS TO SUPPLY KITCHEN COUNTERTOPS (4128) 6. REATTACH PANEL TO WALL & CONDUIT 7. CHECK FOR WORKING SPACE PANEL (4129) |