Permit: T06CM01874

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
07/18/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
05/25/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK #4130
05/24/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. ONLY ONE CONDUCTOR UNDER SCREW TERMINAL - 110.14
2. PROTECT CABLE AT STUDS -- 300.4
3. MAINTAIN FIREWALL SEPARATION
03/05/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK CONDUIT REPAIR
02/27/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
BOXES WITH EXTRA HOLE - REPLACE
OK ROUGH ELECTRIC
02/26/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. REPLACE BROKEN BOXES
2. EXTENDER RINGS MAY BE NEEDED (314.20)

OK NORTH HALF - 10 UNITS
02/22/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
PLANS CALL FOR COMPLIANCE WITH LATEST EDITION OF NEC
ARC FAULTS REQUIRED PER NEC
02/20/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
RECALL INSP. LEAVE MSG. WITH PH.# OF CONTACT PERSON IF NO ONE AT OFFICE.