Permit: T06CM01872

Parcel: 133170630


Addresses:

350 N WILMOT RD

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
04/10/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
03/21/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. 5B-NO7 NEEDS CEILING ACCESS TO FIRE DAMPER
2. 5B-N16 NEED TO RELOCATE DUCT ACCESS DOOR
3. FIRE DAMPER AT 5-19 NO ANGLE, NO DUCT DETECTOR, PROVIDE LARGER ACCESS
4. FIRE DAMPER AT 5-I33 MISSING ANGLE
5. WILL CHECK CORRECTIONS ON MONDAY
6. OK TEMP C OF O ALL FLOORS
03/20/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
- PERMANENTLY I.D ELEVATOR FAN COIL & CONDENSOR ON ROOF
- CONDENSATE DOES NOT HAVE ADEQUATE SLOPE
- EXTEND STEAM CONDENSATE IN FRONT OF AH-05-2, AH-05-4
- SOME DUCT SMOKE DETECTORS MISSING FILTERS
- CHECKED ALL AIR HANDLERS & ROOFTOP EQUIPMENT
- FINISH INSULATING STEAM PIPING
- OK TO FILE FOR TEMP C OF O