Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T06CM01872
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/10/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
03/21/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. 5B-NO7 NEEDS CEILING ACCESS TO FIRE DAMPER 2. 5B-N16 NEED TO RELOCATE DUCT ACCESS DOOR 3. FIRE DAMPER AT 5-19 NO ANGLE, NO DUCT DETECTOR, PROVIDE LARGER ACCESS 4. FIRE DAMPER AT 5-I33 MISSING ANGLE 5. WILL CHECK CORRECTIONS ON MONDAY 6. OK TEMP C OF O ALL FLOORS |
|
03/20/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* - PERMANENTLY I.D ELEVATOR FAN COIL & CONDENSOR ON ROOF - CONDENSATE DOES NOT HAVE ADEQUATE SLOPE - EXTEND STEAM CONDENSATE IN FRONT OF AH-05-2, AH-05-4 - SOME DUCT SMOKE DETECTORS MISSING FILTERS - CHECKED ALL AIR HANDLERS & ROOFTOP EQUIPMENT - FINISH INSULATING STEAM PIPING - OK TO FILE FOR TEMP C OF O |