Inspection Status: Approved
Inspection History: MECHANICAL - PROGRESS
Permit Number - T06CM01872
Inspection Description - MECHANICAL - PROGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/11/2008 | MECHANICAL - PROGRESS | Approved | ||
11/16/2007 | MECHANICAL - PROGRESS | Partial Approval | IVRS - Inspection :* 110 PSI TEST CWS & CWR PIPING FROM CENTRAL PLANT TO NEW BLDG. |
|
08/01/2007 | MECHANICAL - PROGRESS | Partial Approval | IVRS - Inspection :* 100 PSI TEST CHILLED & HEATED WATER LINES CARBON STEEL MAINS TESTED UP TO SHUT OFF VALVES TO COILS 2ND FLOOR THRU PENTHOUSE. |
|
07/25/2007 | MECHANICAL - PROGRESS | Partial Approval | IVRS - Inspection :* 100 PSI TEST HEATING & CHILLED WATER LINES FROM MAIN CONNECTION 1ST FLOOR AREA B TO BASEMENT CHILLED WATER AREA A FROM MAIN CONNECTION ON LEVEL 2 DOWN TO BASEMENT |
|
06/28/2007 | MECHANICAL - PROGRESS | Partial Approval | IVRS - Inspection :* CHECKED HOT WATER PIPING TO VAV COILS 1ST FLOOR & 3RD FLOOR OK TO PROCEED W/INSULATION THIS IS FOR AREA A ONLY & DOWN TO BASEMENT LEVEL. |
|
03/27/2007 | MECHANICAL - PROGRESS | Partial Approval | IVRS - Inspection :* CHECKED CONDENSOR PIPING FROM HEAT EXCHANGES TO GENERATOR 150 PSI TEST OK OK TO INSULATE. |
|
02/26/2007 | MECHANICAL - PROGRESS | Partial Approval | IVRS - Inspection :* OK TO INSULATE DUCTS AFTER SEALANT IS APPLIED. |