Permit: T06CM01872

Parcel: 133170630


Addresses:

350 N WILMOT RD


Inspection Status: Approved

Inspection History: MECHANICAL - PROGRESS

Permit Number - T06CM01872

Inspection Description - MECHANICAL - PROGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
04/11/2008 MECHANICAL - PROGRESS Approved
11/16/2007 MECHANICAL - PROGRESS Partial Approval IVRS - Inspection :*
110 PSI TEST CWS & CWR PIPING FROM CENTRAL PLANT TO NEW BLDG.
08/01/2007 MECHANICAL - PROGRESS Partial Approval IVRS - Inspection :*
100 PSI TEST CHILLED & HEATED WATER LINES CARBON STEEL MAINS TESTED UP TO SHUT OFF VALVES TO COILS 2ND FLOOR THRU PENTHOUSE.
07/25/2007 MECHANICAL - PROGRESS Partial Approval IVRS - Inspection :*
100 PSI TEST HEATING & CHILLED WATER LINES FROM MAIN CONNECTION 1ST FLOOR AREA B TO BASEMENT
CHILLED WATER AREA A FROM MAIN CONNECTION ON LEVEL 2 DOWN TO BASEMENT
06/28/2007 MECHANICAL - PROGRESS Partial Approval IVRS - Inspection :*
CHECKED HOT WATER PIPING TO VAV COILS
1ST FLOOR & 3RD FLOOR OK TO PROCEED W/INSULATION
THIS IS FOR AREA A ONLY & DOWN TO BASEMENT LEVEL.
03/27/2007 MECHANICAL - PROGRESS Partial Approval IVRS - Inspection :*
CHECKED CONDENSOR PIPING FROM HEAT EXCHANGES TO GENERATOR 150 PSI TEST OK
OK TO INSULATE.
02/26/2007 MECHANICAL - PROGRESS Partial Approval IVRS - Inspection :*
OK TO INSULATE DUCTS AFTER SEALANT IS APPLIED.